Download data sheet
smartALERT is an innovative and thoroughly reliable gas warning device. With a highly sensitive IR sensor, smartALERT reacts to the lowest concentrations of gas and produces an alarm long before danger develops. IR measuring technology effectively eliminates irritating false alarms.The gas alarm is divided into a pre- and main alarm and can be supplemented by
additional alarms The different alarm states are eventorientated and supported by clear speech announcements. In case of emergencies, users receive important information on preventing potential danger. Simple assembly and an optional power plug means smartALERT can be installed and operational within minutes. An integrated anti-tamper monitoring system protects the device from wilful interference.
During the development of smartALERT particular attention was paid to the recommendations of DVGW-Arbeitsblatt
G110 (German Gas and Water Association Worksheet G110), and on this basis, smartALERT has been independently
checked and passed as CE and DIN EN 50194-conform for use in domestic homes.
Download_EN50194-Conformity • Gas warning device based on infrared absorption technology
• Models for natural gas, liquid gas or CO2
• DIN EN 50194 compliant
• Integrated anti-tamper monitoring
• Simple and rapid installation
• Event-driven speech commands
• Valve-control on board
• Log book functionality
• Long working life (>10 years)
• Made in Germany
| General features | |
| Gas: | natural gas (methane) / liquid gas (propane, butane) / carbon dioxide (CO2) |
| Measurement principle: | Infrared absorption (NDIR) |
| Measurement range: | 0 to 100 % LEL / 0 to 1 Vol.-% (CO2) |
| Operating temperature: | -15 °C to 45 °C |
| Pressure: | 800 to 1100 hPa |
| Humidity: | 0 % to 95 % rel. humidity |
| Response time t90: | < 30 seconds |
| Warm-up time: | 2 minutes |
| Working life: | 10 years (depending on working environment) |
| Maintenance interval: | every 2 years (recommended) |
| Electrical data | |
| Power supply: | 12 or 24 Volt DC |
| Electronics power consumption: | approx. 3 Watt |
| Output voltage: | 12 or 24 Volt DC – On/Off signal, depending on power supply |
| Output current: | max. 500 mA |
| Housing | |
| Dimensions (L x W X D): | 125 mm x 105 mm x 60 mm |
| Weight: | approx. 0.3 kg |
| Material: | ABS |
| Protection type: | IP 45 |
| Storage temperature: | -25 °C to 60 °C |
| Normen | |
| DIN EN 60335-1 | Household and similar electrical appliances- Safety- Part1 |
| DIN EN 50270 | Electromagnetic compatibility |
| DIN EN 50194-1:2009 | Electrical devices for the detection of combustible gases in domestic housing |